Raychem HTV self-regulating heating cable is designed for freeze protection or process temperature maintenance of pipes and vessels up to 205°C continuously, with a maximum exposure temperature of 260°C.
The HTV cable has a solid construction with a high power retention (HPR) heating core and pressure extruded electrical insulation.
It is then integrated with a robust metallic braid and a chemically resistant fluoropolymer outer jacket.
Features
- High power retention (HPR) heating core
- Power retention: At least 95% after 10 years
- Design life: 30 years or more depending on application
- Simplified design in hazardous area: T3 and T2
- Longer circuit lengths due to larger cross section conductors
- Fast installation: cut-to-length, multiple overlaps allowed, meter markings, user-friendly connections kits
Specifications
Area Classification: Non-Hazardous; Hazardous
Ground Path Type: Braid
Max Cumulative Hours for Intermittent Exposure: 2000 h
Max Intermittent Exposure Temperature, Power On/Off: 500 °F
Max Maintain or Continuous Exposure Temperature, Power On: 400 °F
Outer Jacket Material: High Temperature Fluoropolymer
| Catalog Number | Item Name | Nominal Power Output @ 50°F, 120V | Nominal Power Output @ 50°F, 240V | Supply Voltage |
| P000004312 | 3HTV1-CT | 3 W/ft | 90 – 130 V | |
| P000004313 | 5HTV1-CT | 5 W/ft | 90 – 130 V | |
| P000004314 | 8HTV1-CT | 8 W/ft | 90 – 130 V | |
| P000004315 | 10HTV1-CT | 10 W/ft | 90 – 130 V | |
| P000004316 | 12HTV1-CT | 12 W/ft | 90 – 130 V | |
| P000004317 | 15HTV1-CT | 15 W/ft | 90 – 130 V | |
| P000004318 | 20HTV1-CT | 20 W/ft | 90 – 130 V | |
| P000004319 | 3HTV2-CT | 3 W/ft | 190 – 277 V | |
| P000004320 | 5HTV2-CT | 5 W/ft | 190 – 277 V | |
| P000004321 | 8HTV2-CT | 8 W/ft | 190 – 277 V | |
| P000004322 | 10HTV2-CT | 10 W/ft | 190 – 277 V | |
| P000004323 | 12HTV2-CT | 12 W/ft | 190 – 277 V | |
| P000004324 | 15HTV2-CT | 15 W/ft | 190 – 277 V | |
| P000004325 | 20HTV2-CT | 20 W/ft | 190 – 277 V | |
| 2000003152 | 28HTV2-CT | 28 W/ft | 190 – 277 V |
Download
| Datasheet | RAYCHEM-DS-H86869-HTV-EN |
| Installation Manual | RAYCHEM-IM-H57274-SelfRegPowerLimHeatTrac-EN |
| Design Guide | Raychem-DG-H56882-SelfRegulating-EN |
Engineering Inquiry: Heating Cable Design & Selection
Please provide me with the following information:
- Country Name?
- Plant Name?
- Ambient Minimum Temperature?
- Process Liquid?
- Process Temperature?
- Maintain Temperature?
- Design Temperature?
- Insulation Material?
- Insulation Thickness?
- Voltage?