Raychem XTVR self-regulating trace heating cables are mainly used for freeze protection of pipes and vessels that require steam cleaning and process temperature maintenance, up to 302 °F/150 °C. They withstand intermittent exposure to 482 °F/250 °C. The fluoropolymer outer jacket (-CT) provides high chemical resistance against aggressive organics and corrosives.
Features
- High power retention (HPR) heating core
- Power retention: At least 95% after 10 years
- Design life: 30 years or more depending on application
- Simplified design in hazardous area: T3 Unconditional or T6-T4 System classification
- Longer circuit lengths due to larger cross section conductors
- Fast installation: cut-to-length, multiple overlaps allowed, meter markings, user-friendly connections kits
Specifications
- Area Classification: Non-Hazardous; Hazardous
- Ground Path Type: Braid
- Max Cumulative Hours for Intermittent Exposure: 2000 h
- Max Intermittent Exposure Temperature, Power On/Off: 482 °F
- Max Maintain or Continuous Exposure Temperature, Power On: 302 °F
- Outer Jacket Material: High Temperature Fluoropolymer
| Catalog Number | Item Name | Nominal Power Output @ 50°F | Supply Voltage | Unit Price US$/Meter |
| 2000003070 | 3XTVR2-CT | 3 W/ft | 200 – 277 V | |
| 2000003072 | 5XTVR2-CT | 5 W/ft | 200 – 277 V | |
| 2000003073 | 8XTVR2-CT | 8 W/ft | 200 – 277 V | |
| 2000003075 | 10XTVR2-CT | 10 W/ft | 200 – 277 V | |
| 2000003076 | 12XTVR2-CT | 12 W/ft | 200 – 277 V | |
| 2000003078 | 15XTVR2-CT | 15 W/ft | 200 – 277 V | |
| 2000003080 | 20XTVR2-CT | 20 W/ft | 200 – 277 V | |
| 2000003071 | 5XTVR1-CT | 5 W/ft | 100 – 130 V | |
| 2000003074 | 10XTVR1-CT | 10 W/ft | 100 – 130 V | |
| 2000003077 | 15XTVR1-CT | 15 W/ft | 100 – 130 V | |
| 2000003079 | 20XTVR1-CT | 20 W/ft | 100 – 130 V |